Guide · Utilities ·
Digging safely near buried services: what HSG47 expects
HSE’s guidance rests on three things: plans, locating and safe digging. What it asks of whoever plans the job and of the crew, the records worth keeping, and where Northern Ireland and Ireland differ.
500mm The gap HSG47 and the HSA code advise between hand-held power tools and the indicated line of a buried cable
HSE’s HSG47, Avoiding danger from underground services, covers any work that breaks the ground: street works, road works, excavation, drilling, piling, demolition and site investigation. Its starting point is simple. Assume services are present unless you have been shown otherwise.
HSG47 is guidance. HSE says following it will normally be enough to comply with the law, and inspectors may refer to it. The legal duty is regulation 25(4) of the Construction (Design and Management) Regulations 2015: work that could create a risk from an underground service must not start until suitable and sufficient steps have been taken to prevent that risk, so far as is reasonably practicable.
Three parts, all needed
The safe system has three parts that work together: planning, locating (a detection survey and trial holes to find, identify and mark services) and safe digging. Plans without a scan, or a scan without careful digging, leave a gap.
Who does what at the planning stage
- Clients: make reasonable enquiries about services and pass what they find to designers and contractors, or give the contractor the time and resources to do it.
- Designers: design the risk out (re-site the services, move the structure, arrange a disconnection) and put what remains on the working drawings. Services should not be built over or encased in concrete.
- Contractors: assess the risks, set a safe system of work, and make sure crews have the information, training and supervision to follow it before they reach site.
- Emergency work: still needs planning. With no plans available, dig as though services are there.
Plans
Ask every owner who may have apparatus in the area. There can be several for one kind of service, such as street lighting, independent networks or private pipes on industrial sites. Where plans show gas at 2 bar or more, speak to the owner before work starts.
Treat plans as a guide only. HSG47 warns that they are not always drawn to scale, kerb lines and levels change, service connections are often not shown, and a missing record never proves the ground is clear. The National Underground Asset Register (NUAR), covering England, Wales and Northern Ireland, now has a statutory basis, but the regulations requiring owners to load and keep their records there are still being finalised, and the same caution applies to it.
Locating and marking
- Trained operators: anyone using a locator needs training in it and its limits, and it should be checked and calibrated as the maker says.
- More than one mode: power mode misses cables carrying little or no current, such as street lighting by day. Add radio mode and, wherever possible, a signal generator, which HSG47 says greatly improves accuracy.
- Known blind spots: locators miss plastic pipes without a tracer wire, and can read two close services as one.
- Trial holes: trace services across the whole work area, then confirm position and depth by hand.
- Marking: paint, chalk or crayon on hard surfaces and wooden pegs on grass, set to one side of the line. No steel pins or spikes.
Safe digging
- Brief the crew: with a written plan of what is where, the right tools and protective clothing, and enough time.
- Keep power tools back: where practicable, at least 500mm from the indicated line of a cable in or under a hard surface, then hand dig to find it. Only break out directly above a service that has been exposed and lies at least 300mm below the hard surface, or is physically protected.
- Dig beside, not on top: make the final exposure by digging in from the side, use insulated tools near cables, ease spades in rather than spiking them, and re-scan as cover comes off.
- Control the excavator: a second person, outside the reach of the arm and bucket, watches into the excavation. No excavators within 500mm of a gas pipe. If a cable is struck, the driver stays in the cab.
- Treat unknowns as live: black plastic is an electricity cable and an iron or steel pipe is gas until proved otherwise.
- Backfill with care: replace warning tape and tiles, keep hardcore out, and keep concrete at least 300mm from gas pipes.
If something is hit
For gas, do not try a repair. Clear the area and nearby buildings, keep ignition sources at least 5m away and call the emergency number in the table below. For a cable, keep everyone away from the excavation, the machine and the cable until the owner has made it safe. Report any damage, however slight, to the owner.
In Great Britain a cable strike can be a reportable dangerous occurrence under RIDDOR 2013, for example where the fire or explosion could have killed someone or the cable is out of action for more than 24 hours. Northern Ireland reports to HSENI under its own 1997 regulations, and in Ireland dangerous occurrences go to the HSA.
What to record
- Enquiries: which owners were asked for plans, when, and what came back.
- Survey: results on the crew’s working drawings, with the locator checks and who did the scan.
- Disconnections: where and when, with the owner’s written confirmation.
- Differences: services found away from their recorded line. Tell the owner, ideally before backfilling.
- As laid: services found or newly installed, passed to the client and the owners on completion, as laid rather than as designed.
Street works qualifications
On street works the law also requires a qualified supervisor, and at least one qualified operative on site while the works are in progress: section 67 of the New Roads and Street Works Act 1991 in England and Wales (Scotland has a matching section) and article 27 of the Street Works (Northern Ireland) Order 1995.
Northern Ireland
The law mirrors Great Britain’s in its own instruments. Regulation 24(4) of the Construction (Design and Management) Regulations (Northern Ireland) 2016 is worded the same as the GB rule, and HSENI enforces it. HSENI’s safety alert on work near underground cables points to HSG47 and asks for the same controls: map and mark cable runs, use locators, and dig safely.
Republic of Ireland
The HSA’s Code of Practice for Avoiding Danger from Underground Services, in effect since 30 May 2016, uses the same three elements and the same 500mm power tool margin. It is a statutory code under section 60 of the Safety, Health and Welfare at Work Act 2005: not following it is not an offence in itself, but it can be used as evidence in a prosecution. It goes further in places.
- Cards: under the Construction Regulations 2013, anyone locating underground services needs a CSCS card as well as Safe Pass.
- Gas transmission pipelines: these run at 7 to 85 bar. Consult the operator before digging within 10 metres, with no mechanical excavation within 3 metres and no hand-held power tools within 1.5 metres unless agreed.
- Trenchless work: keep 300mm (HSG47 says 250mm) or one and a half times the pipe diameter from other services, whichever is greater, and do not mole or drill directionally within 10 metres of a gas pipeline without consulting the operator.
| Topic | Great Britain | Northern Ireland | Ireland |
|---|---|---|---|
| Main guidance | HSE’s HSG47 (2014) | HSG47, which HSENI points to | HSA code of practice (2016) |
| Standing | Guidance: following it normally complies with the law | Guidance, as in GB | Statutory code, usable as evidence in a prosecution |
| Regulator | HSE | HSENI | HSA |
| Gas emergency | 0800 111 999 | 0800 002 001 | 1800 20 50 50 |
This guide is general information, not legal advice. Guidance is revised from time to time: check the current position with HSE, HSENI or the HSA, and follow each service owner’s own requirements, before relying on it.
Sources
- HSE: Avoiding danger from underground services, HSG47 (third edition, 2014)
- legislation.gov.uk: Construction (Design and Management) Regulations 2015, regulation 25
- legislation.gov.uk: Construction (Design and Management) Regulations (Northern Ireland) 2016, regulation 24
- legislation.gov.uk: New Roads and Street Works Act 1991, section 67
- legislation.gov.uk: Street Works (Northern Ireland) Order 1995, article 27
- HSENI: Safety alert, work near underground cables (12 June 2020)
- HSA: Code of Practice for Avoiding Danger from Underground Services (2016)
- Phoenix Energy: Northern Ireland gas emergency number
- Gas Networks Ireland: gas emergency number
- GOV.UK: National Underground Asset Register tranche 1 regulations, consultation
- GDS Geospatial blog: Towards a comprehensive National Underground Asset Register (28 January 2026)